|
6/14 outputs, measuring voltage common with supply voltage
Production stopped. See NOVAR 1106/1114 for replacement. Power factor controllers NOVAR 106 and NOVAR 114 are fully automatical instruments designated to optimal control over compensation of reactive power. Both are intended mostly for demanding applications.
Characteristics - For demanding applications
- 6 or 14 relay outputs + alarm relay
- Common supply and measuring voltage 230 V AC (or 115 V AC), 50/60 Hz
- Measuring current sensitivity 0,01 A
- High resistance against electromagnetic interference
- Front panel 144 x 144 mm with high efficient LED-display
- Optional communication interface
Related Documents General Description The NOVAR 106, 114 reactive power governor is a fully automatic instrument that allows optimum control of reactive power compensation. It contains precise voltage and current measurement circuits, and high precision evaluation of both root-mean-square (RMS) current and the power factor is achieved through digital processing of the values measured. The 230 V AC supply terminals also work as the measurement voltage input. The current measurement input is a general-purpose one for the nominal secondary winding current value of a current measuring transformer (CMT) 1A or 5A. Current of any of the phases can be measured. The instrument calculates the fundamental harmonic component of the active and reactive currents using the FFT algorithm. Thus precise measurement and control are provided even if the current waveform is distorted by higher harmonic components. Controlling takes place in all four quadrants and its speed depends on both control deviation value and its polarization (overcompensation / undercompensation). Connecting and disconnecting power factor capacitors is carried out to achieve the optimum compensation condition with a single control step and minimum number of switching on or off the sections. At the same time, the instrument chooses the sections with regard to their even load and preferably connects those that have been disconnected for the longest time and the remaining charge of which is thus minimum. While controlling, the instrument continually checks the compensation sections. If a section drop-out or value alteration is detected, the section is temporarily disabled at relevant setting. The section temporarily disabled is periodically tested, while control is in progress, and possibly enabled again. In measurement of current, harmonic component levels are evaluated of up to the nineteenth order. The total harmonic distortion (THD) is calculated from these measurements and can be viewed on a display. It is possible to preset the THD threshold level at which the governor disconnects all compensation sections thus preventing their damage. Besides that, the most adverse THD values, values of harmonic components selected and the minimum power factor values are recorded into the instrument memory for subsequent analysis. Fully automatic installation is advantage of the instrument. The governor automatically detects both the mode of the current measured connection and the value of each compensation section connected. Entering these parameters manually is also possible. The "Alarm" relay output can be set to indicate non-standard conditions, such as undercurrent, overcurrent, harmonic distortion preset threshold exceeded, overcompensation or undercompensation, section limit connection rate exceeded, section drop-out or reverse supply condition. The governors are supplied in two basic versions with different numbers of outputs: NOVAR 106 with six output relays and NOVAR 114 with fourteen output relays. The governors can be ordered in a version with galvanically isolated RS 223 or RS 485 standard communication interface. All values measured can be monitored and the governor parameters set using a remote computer. Besides the power factor capacitors, it is possible to connect up to ten compensatory chokes (mains decompensation). Any output can be set as fixed. Characteristics and Features Measurement principles - high current and power factor measurement accuracy is achieved by utilizing digital signal processing using a microprocessor and FFT algorithm
- precise measurement and control functions even under conditions of voltage or current waveform distortion by higher harmonic components
- evaluation of current total harmonic distortion (THD) level by up to the nineteenth harmonic component and display of the instantaneous THD value including the levels of the 3rd, 5th, 7th, 11th, 13th, and 17th harmonic components.
Control principles - governor´s speed of response independently programmable for conditions of undercompensation and overcompensation, respectively
- the preset speed of response increases in proportion to instantaneous control deviation, that is by square of the ratio of the control deviation to the smallest capacitor section value (C/k); growing control deviation may reduce this value to minimum control time of 5 seconds.
- if the control deviation is smaller than the smallest capacitor section current (C/k), the preset control response time gets longer twofold; if the control deviation keeps decreasing under a half of the smallest capacitor section current (C/k), no control takes place
Automatic connection detection - automatic connection detection on governor installation as shown in the following table
Tab. 1 : Measuring (and supply) voltage connection in respect to current signal connected | No. | Mode of connection | | 1 | L1-0 | | 2 | L2-0 | | 3 | L3-0 | | 4 | 0-L1 | | 5 | 0-L2 | | 6 | 0-L3 | Automatic control section recognition - with appropriate setting, when switching it on, the governor automatically recognizes the sections´ currents
- It is possible to connect any combination of the control sections
- section value manual entry using the C/k value and the switching program as described in the table below or direct entering of the value of each section
Tab. 2 : Switching program | No. | combination | displayed | è. | combination | displayed | | 1 | 1:1:1:1:1 | 1111 | 7 | 1:2:2:2:2 | 1222 | | 2 | 1:1:2:2:2 | 1122 | 8 | 1:2:3:3:3 | 1233 | | 3 | 1:1:2:2:4 | 11224 | 9 | 1:2:3:4:4 | 1234 | | 4 | 1:1:2:3:3 | 1123 | 10 | 1:2:3:6:6 | 1236 | | 5 | 1:1:2:4:4 | 1124 | 11 | 1:2:4:4:4 | 1244 | | 6 | 1:1:2:4:8 | 11248 | 12 | 1:2:4:8:8 | 1248 | Specifying section value - continuous specification of section value recognized in the control process
Disabling faulty sections - continuous checking of control sections in the control process and in case of repeated failure detection, temporary disablement of the faulty section and possibly concurrent alarm actuation
- periodic recheck of the temporarily disabled sections in five days and on positive test results (for example when replacing a burnt fuse link in section) enabling them again
Fixed sections - any control section can be set as fixed, that is as constantly connected or constantly disconnected
Alarm with free program - independently adjustable alarm´s signaling and action functions in accordance with the tables below
- a LED is provided for signaling on the front panel and a contacless "Alarm" switch
Tab. 3: Alarm signaling | No. | condition | description | min. time | | 1 | undercurrent | current measuring transformer secondary winding current below 0.01 A | 5 seconds | | 2 | overcurrent | current measuring transformer secondary winding current over preset nominal value (5A/1A) | 5 seconds | | 3 | compensation error | power factor beyond range 0.9 L ÷ 1.00 | 15 minutes | | 5 | harmonic distortion | THD preset threshold level exceeded functional with loads 10% plus | 5 minutes | | 6 | number of connections exceeded | the number of connections of a section exceeded preset limit | immediately | | 8 | reverse supply | power flow from appliance to source detected | 5 minutes | | 9 | section failure | constant section value deviation detected in control process (most often section dropout) | 5 connections + 5 disconnections | Note: The conditions printed in bold are preset as standard. Tab. 4 : Alarm action | No. | condition | description | min. action time | action | | 1 | undercurrent | current measuring transformer secondary winding current below 0.01 A | 10 seconds | disconnection of all outputs except the fixed ones | | 5 | harmonic distortion | THD preset threshold level exceeded functional with loads 10% plus | 5 minutes | disconnection of all outputs (including the fixed ones) | | 8 | reverse supply | power flow from appliance to source detected | 5 minutes | disconnection of all outputs except the fixed ones | | 9 | section failure | constant section value deviation detected in control process (section dropout) | 5 connections + 5 disconnections | section disabled | Note: The conditions printed in bold are preset as standard. 
Communication OptionsAll types of power factor controller include an option al, galvanically isolated communication line - either RS232 or RS485. It enables remote monitoring of all the measured values, state and also perform configuration of the device. For communication with the device there are two similar protocols available - MODBUS and KMB. Both protocols are documented and publicly available. Software for data acquisition and processing is also available. The basic version of the RETIS software is free of charge and can be downloaded from our web site. . | interface | RS232/RS485, galvanically isolated | | speed | 4800 to 19200 Bd | | maximum devices on a comm line | 1 / 32 | | max distance of two nodes | 30 m / 1200 m | | Communication protocol | KMB, Modbus RTU | Accessories for for Reactive Power Compensation
With our power factor controllers we also supply all other necessary components - compensation capacitors, chokes, contactors, current transformers and other. For mor information and quotes please contact us. | LV and HV capacitors form ZEZ Silko |  Affordable compensation and de-compensation chokes by ELEKTRA | PEWATRON's current transformers with both compact and split cores (X/5 and X/1) | Benedict&Jager contactors
| IP 65 COVER - transparent plastic cover to improve front panel protection (IP-65)
- availavle for booth 96x96 and 144x144 mm
Technical Parameters | Adjustable parameters | | power factor desired | 0.80 ind. through 0.90 cap. | | connection time (ma. value, depends on control deviation) | 5 to 1 200 seconds | | reconnection lockout time | 5 to 1 200 seconds | | smallest capacitor current (C/k value converted to CMT primary side) | (0.01 ÷ 2 A) x CMT ratio | | choke control limit power factor | 0.80 ind. through 0.90 cap. | | setting compensation section values | automatic or manual | | setting connection mode | automatic or manual | | InputsOutputs | | measuring voltage (galvanically isolated) | shared with supply voltage | | measuring current (galvanically isolated) | 0,01 to 7,5A | | current input serial impedance | <10 mΩ | | current measurement accuracy (RMS value and 1st harmonic) | ± 1% ± 0,01A | | harmonic component and THD measurement accuracy | ± 10% | | number of output relays | 6 or 14 | | output relay load rating | 250 V AC / 4 A | | "alarm" relay load rating | 250 V AC / 4 A | | power supply | 230 V AC +10/-20%, max. 10 VA | | installation overvoltage class | II in compliance with EN 61010-1 | | Telecommunication | | interface | RS232/RS485, galvanically isolated | | transmission rate | 9600 Baud | | maximum number of instrument on one communication line | 1/32 | | maximum nodetonode distance | 30 m / 1200 m | | Operating conditions | | working environment | in compl. with IEC 654-1, class C1 | | operating temperature | -40° ÷ +60° C | | relative humidity | 5 to 100 % | | EMC | | noise suppression level in compliance with: | EN 50081-2 EN 55011 , class A EN 55022 , class A | | immunity | EN 61000-6-2 | | Mechanical | enclosure: - front panel - back panel | IP40 (or IP54) IP 20 | dimensions: - front panel - builtin depth | 230 x 105 x 320 mm 144 x 144 mm 80 mm | | Mass | max. 1,0 kg | |