Products
News
Software
Docs and Download
Meinberg
Search
Contacts
About KMB
  • cesky
Related Products
Popular
Address
KMB systems, s.r.o

Dr. M. Horakove 559
46006 Liberec 7
Czech Republic

ISO

The company manages quality improvement processes according to CSN EN 9001:2001

ISO

We participate in the process that defines future development of the region.

 

NOVAR 11xx a 12xx Print
New line of PFC with enhanced sensitivity, 6/14 outputs

NOVAR 1114NOVAR 1xxx-line power factor controllers are fully automatic instruments designated for optimal compensation of reactive power. They are suitable for PFC application which requires precise control even under low load. These new products are compatible (in terms of wiring) with previos NOVAR 1xx devices.

Characteristics

  • 6 or 14 relay outputs + alarm relay
  • Measuring current sensitivity 0,002 A
  • Embedded temperature sensor, cooler fan/heating control
  • Front panel 144 x 144 mm with high efficient LED-display
  • Optional communication interface

Device Types

Tab. 1: NOVAR 1xxx Overview.
Type Nr. of outputs Measuring voltage 2nd tariff
NOVAR 1106 6 100-275 V AC, 43 ÷ 67 Hz
Common supply and measuring voltage
no
NOVAR 1114 14
NOVAR 1206 6 57,7 - 690 V AC +10/-20%, 43 ÷ 67 Hz
Separated supply voltage
yes
NOVAR 1214 14
Tab. 2: power supply versions
versionStandard
S400
power supply100 - 275 V AC 75 - 500 V AC/DC
common pole of relay Internally connected with "L" power supply terminal
isolated, connected to additional terminals

Related Documents

Communication scheme example

Communication Options

All types of power factor controller include an option al, galvanically isolated communication line - either RS232 or RS485. It enables remote monitoring of all the measured values, state and also perform configuration of the device.  For communication with the device there are two similar protocols available - MODBUS and KMB. Both protocols are documented and publicly available.

Software for data acquisition and processing is also available. The basic version of the RETIS software is free of charge and can be downloaded from our web site.

.

 

 

 

interface RS232/RS485, galvanically isolated
speed 4800 to 19200 Bd
maximum devices on a comm line 1 / 32
max distance of two nodes 30 m / 1200 m
Communication protocol KMB, Modbus RTU

Accessories for for Reactive Power Compensation

With our power factor controllers we  also supply all other necessary components - compensation capacitors, chokes, contactors, current transformers and other. For mor information and quotes please  contact us.
Chokes
LV and HV capacitors form ZEZ Silko
Chokes
Affordable compensation and de-compensation  chokes by  ELEKTRA
Current Transformers
PEWATRON's current transformers with both compact and split cores (X/5 and X/1)
Contactors
Benedict&Jager contactors

IP 65 COVER

  • transparent plastic cover to improve front panel protection (IP-65)
  • availavle for booth 96x96 and 144x144 mm

Technical Parameters

Adjustable parameters

power factor desired 0.80 ind. through 0.80 cap.
connection time (ma. value, depends on control deviation) 5 to 1 200 seconds
reconnection lockout time 5 to 1 200 seconds
smallest capacitor current (C/k value converted to CMT primary side) (0.002 ÷ 2 A) x CMT ratio
choke control limit power factor 0.80 ind. through 0.80 cap.
setting compensation section values automatic or manual
setting connection mode automatic or manual

Inputs–Outputs

power supply 110 ÷ 275 V AC, 43÷ 67 Hz, max. 7 VA
measuring voltage  
NOVAR 1106/1114 the same as power supply voltage
NOVAR 1206/1214 57.7 ÷ 690 V AC +10/-20%, 43 ÷ 67 Hz
voltage measurement accuracy (RMS value and 1st harmonic) ±1% ±1 digit
voltage input impedance (NOVAR 1206/1214) > 800 kΩ
measuring current (galvanically isolated) 0,002 to 7 A
current input serial impedance < 10 mΩ
current measurement accuracy (RMS value and 1st harmonic) ±1% ±1 digit
harmonic component and THD measurement accuracy ±5% ±1 digit (for U,I > 10% of range)
temperature measurement range / accuracy -30 ÷ 60 °C, ± 5 °C
number of output relays 6 or 14
output relay load rating 250 V AC / 4 A
“alarm” relay load rating 250 V AC / 4 A
second metering rate input (galvanically connected, for connection of insulated contact optron 30 Vss / 5 mA
installation overvoltage class / pollution degree  
for measuring voltage up to 300 V AC III-2 in compliance with EN 61010-1
for measuring voltage over 300 V AC II-2 in compliance with EN 61010-1

Operating conditions

working environment class C1 in compliance with IEC 654-1
operating temperature ­-40° ÷ +60°C
relative humidity 5 to 100 %

EMC

noise suppression level in compliance with: EN 50081-2
EN 55011 , class A
EN 55022 , class A
immunity in compliance with EN 61000-6-2

Mechanical

enclosure  
front panel IP40 (or IP54)
back panel IP20
dimensions  
front panel 144 x 144 mm
built-in depth 80 mm
cutout 138 x 138 mm
mass max. 0.7 kg
 
Next >