|
New line of PFC with enhanced sensitivity, 6/14 outputs NOVAR 1xxx-line power factor controllers are fully automatic instruments designated for optimal compensation of reactive power. They are suitable for PFC application which requires precise control even under low load. These new products are compatible (in terms of wiring) with previous NOVAR 1xx devices.
Characteristics - 6 or 14 relay outputs + alarm relay
- Measuring current sensitivity 0,002 A
- Embedded temperature sensor, cooler fan/heating control
- Front panel 144 x 144 mm with high efficient LED-display
- Optional communication interface
Related Documents
Communication OptionsNOVAR power factor controllers do include an optional galvanically isolated communication line - either RS485 or Ethernet. It enables remote monitoring of all the measured values, states and also perform configuration of the device. For communication with the device there are two similar protocols available - MODBUS and KMB. Complete setup, parametrization and data analysis can be performed with ENVIS v.1.1 software suite free of charge. The licenced ENVIS.Online system service can also automatically monitor and record the measurements from NOVAR PFC. If predefined condition is met ENVIS sends out an alarm (email, SMS, SNMP Trap). The older software RETIS can be also used to manage these PFCs with limited set of features. Accessories for for Reactive Power Compensation
With our power factor controllers we also supply all other necessary components - compensation capacitors, chokes, contactors, current transformers and other. For mor information and quotes please contact us. | LV and HV capacitors form ZEZ Silko |  Affordable compensation and de-compensation chokes by ELEKTRA | PEWATRON's current transformers with both compact and split cores (X/5 and X/1) | Benedict&Jager contactors
| IP 65 COVER - transparent plastic cover to improve front panel protection (IP-65)
- availavle for booth 96x96 and 144x144 mm
Device Types Tab. 1: NOVAR 1xxx Overview. | Type | Nr. of outputs | Measuring voltage | 2nd tariff | | NOVAR 1106 | 6 | 100-275 V AC, 43 ÷ 67 Hz Common supply and measuring voltage | no | | NOVAR 1114 | 14 | | NOVAR 1206 | 6 | 57,7 - 690 V AC +10/-20%, 43 ÷ 67 Hz Separated supply voltage | yes | | NOVAR 1214 | 14 | Tab. 2: power supply versions
| version | Standard
| S400 | | power supply | 100 - 275 V AC | 75 - 500 V AC/DC
| | common pole of relay | Internally connected with "L" power supply terminal
| isolated, connected to additional terminals
| Technical ParametersAdjustable parameters | power factor desired | 0.80 ind. through 0.80 cap. | | connection time (ma. value, depends on control deviation) | 5 to 1 200 seconds | | reconnection lockout time | 5 to 1 200 seconds | | smallest capacitor current (C/k value converted to CMT primary side) | (0.002 ÷ 2 A) x CMT ratio | | choke control limit power factor | 0.80 ind. through 0.80 cap. | | setting compensation section values | automatic or manual | | setting connection mode | automatic or manual | Inputs–Outputs | power supply | 110 ÷ 275 V AC, 43÷ 67 Hz, max. 7 VA | | measuring voltage | | | NOVAR 1106/1114 | the same as power supply voltage | | NOVAR 1206/1214 | 57.7 ÷ 690 V AC +10/-20%, 43 ÷ 67 Hz | | voltage measurement accuracy (RMS value and 1st harmonic) | ±1% ±1 digit | | voltage input impedance (NOVAR 1206/1214) | > 800 kΩ | | measuring current (galvanically isolated) | 0,002 to 7 A | | current input serial impedance | < 10 mΩ | | current measurement accuracy (RMS value and 1st harmonic) | ±1% ±1 digit | | harmonic component and THD measurement accuracy | ±5% ±1 digit (for U,I > 10% of range) | | temperature measurement range / accuracy | -30 ÷ 60 °C, ± 5 °C | | number of output relays | 6 or 14 | | output relay load rating | 250 V AC / 4 A | | “alarm” relay load rating | 250 V AC / 4 A | | second metering rate input (galvanically connected, for connection of insulated contact optron | 30 Vss / 5 mA | | installation overvoltage class / pollution degree | | | for measuring voltage up to 300 V AC | III-2 in compliance with EN 61010-1 | | for measuring voltage over 300 V AC | II-2 in compliance with EN 61010-1 | Operating conditions | working environment | class C1 in compliance with IEC 654-1 | | operating temperature | -40° ÷ +60°C | | relative humidity | 5 to 100 % | EMC | noise suppression level in compliance with: | EN 50081-2 EN 55011 , class A EN 55022 , class A | | immunity | in compliance with EN 61000-6-2 | Mechanical | enclosure | | | front panel | IP40 (or IP54) | | back panel | IP20 | | dimensions | | | front panel | 144 x 144 mm | | built-in depth | 80 mm | | cutout | 138 x 138 mm | | mass | max. 0.7 kg | |