Fast NOVAR 1312 Print
For fast compensation, improved sensitivity, 12+2 outputs

NOVAR 1312NOVAR 1312 and NOVAR 1312-3 reactive power controllers (governor, PFC) is designed for compensation systems where conventional governors with relay outputs to control circuit breakers do not meet special requirements. These are usually systems where rapid frequent changes in reactive power take place or systems with strict requirements on electromagnetic noise suppression and power quality.

 The governor allows up to 25 control interventions per second. Together with KATKA thyristor switching modules, it provides optimal control of reactive power compensation. 

Combined compensation systems utilizing both thyristor switching modules and circuit breakers are also possible to be build with this governor.

NOVAR 1312-3 differs in that it has three current inputs and process sum of all three phase current signals. Therefore, it allows fast compensation according three-phase power factor. 

Related Documents

Communication scheme example

Communication Options

NOVAR power factor controllers do include an optional galvanically isolated communication line - either RS485 or Ethernet. It enables remote monitoring of all the measured values, states and also perform configuration of the device.  For communication with the device there are two similar protocols available - MODBUS and KMB.

Complete setup, parametrization and data analysis can be performed with ENVIS v.1.1 software suite free of charge. The licenced ENVIS.Online system service can also automatically monitor and record the measurements from NOVAR PFC. If predefined condition is met ENVIS sends out an alarm (email, SMS, SNMP Trap). The older software RETIS can be also used to manage these PFCs with limited set of features.

Accessories for for Reactive Power Compensation

With our power factor controllers we  also supply all other necessary components - compensation capacitors, chokes, contactors, current transformers and other. For mor information and quotes please  contact us.
Chokes
LV and HV capacitors form ZEZ Silko
Chokes
Affordable compensation and de-compensation  chokes by  ELEKTRA
Current Transformers
PEWATRON's current transformers with both compact and split cores (X/5 and X/1)
Contactors
Benedict&Jager contactors

IP 65 COVER

  • transparent plastic cover to improve front panel protection (IP-65)
  • availavle for booth 96x96 and 144x144 mm

Technical parameters

Adjustable parameters

power factor desired 0.80 ind. through 0.80 cap.
control speed 1 to 25 control interventions in one second
reconnection lock–out time 0.1 to 10 seconds
smallest capacitor current (C/k value converted to CMT primary side) (0.002 ÷ 2 A) x CMT ratio
choke control limit power factor 0.80 ind. through 0.80 cap.
setting compensation section values automatic or manual
setting connection mode automatic or manual

Inputs–Outputs

power supply 100 ÷ 275 V AC, 43÷ 67 Hz, max. 7 VA
measuring voltage 57.7 ÷ 690 V AC +10/-20%, 43÷ 67 Hz
voltage measurement accuracy (RMS value and 1st harmonic) ±1% ± digit
voltage input impedance > 800 kΩ
measuring current (galvanically isolated) 0,002 to 7 A
current input serial impedance < 10 mΩ
current measurement accuracy (RMS value and 1st harmonic) ±1% ±1 digit
harmonic component and THD measurement accuracy ±5% ± 1 digit (for U,I > 10% of range)
temperature measurement range / accuracy -30 to 60 °C, ± 5 °C
number of outputs in transistor section 12
output transistor load capacity maximum 100V / 100 mA
number of output relays 2
output relay load rating 250 V AC / 4 A
“alarm” relay load rating 250 V AC / 4 A
second metering rate input (galvanically connected, for connection of insulated contact optron 30 Vss / 5 mA
installation overvoltage class / pollution degree for measuring voltage up to 300 V AC
for measuring voltage over 300 V AC III-2 in compliance with EN 61010-1

II-2 in compliance with EN 61010-1

Operating conditions

working environment class C1 in compliance with IEC 654-1
operating temperature ­40° ÷ +60°C
relative humidity 5 to 100 %

EMC

noise suppression level in compliance with EN 50081-2
EN 55011 , class A
EN 55022 , class A
immunity in compliance withEN 61000-6-2

Mechanical

enclosure  
- front panel IP40 (or IP54)
- back panel IP20
dimensions  
- front panel 144 x 144 mm
- built-in depth 80 mm
- cutout 138 x 138 mm
mass max. 0.7 kg
 